Figure 4 Drain
Grounding Reel Feet.

OPERATOR AND FIELD MAINTENANCE MANUAL FOR TANK UNIT, FUEL DISPENSING, TRAILER MOUNTING: FUEL DISTRIBUTION SYSTEM
Page Navigation
  162    163    164    165    166  167  168    169    170    171    172  
img
. . . . .
0031
TM 10-4930-369-13&P
FIELD MAINTENANCE
REPLACE GROUNDING REEL
INITIAL SETUP:
Personnel Required
Tools and Special Tools
Quartermaster and Chemical Equipment
GMTK (WP 0063, Item 7)
Repairer 91J
Materials/Parts
Equipment Condition
Gloves, Leather Work (WP 0062, Item 12)
Washer, Split (WP 0064, Item 7)
FDS disconnected from power source (WP 0005)
WARNING
Maintenance must not be performed on equipment that is operating. Failure to comply may
result in injury or death to personnel.
REPLACE
Remove Grounding Reel
1.  Remove the four hex head cap screws (Figure 1, Item 2) and four lock washers (Figure 1, Item 1). Retain the
cap screws and discard lock washers.
Figure 1.
Grounding Reel.
2.
Lift the grounding reel (Figure 1, Item 4) from the mounting plate (Figure 1, Item 3).