• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
Toggle Switch OFF.
Figure 22. Drained Pan Beneath Pump Inlet.

OPERATOR AND FIELD MAINTENANCE MANUAL FOR TANK UNIT, FUEL DISPENSING, TRAILER MOUNTING: FUEL DISTRIBUTION SYSTEM
Page Navigation
  34    35    36    37    38  39  40    41    42    43    44  
img
0005
TM 10-4930-369-13&P
Figure 21. Fuel Nozzle Housing.
6.
Place crank handle in handle tube or stow in cargo container.
7.
Disconnect ground clip from fueled equipment and retract cable into grounding reel.
END OF TASK
DRAINING THE FUEL DISTRIBUTION SYSTEM
WARNING
When handling fuel, personnel must take appropriate measures to minimize the risk of ire,
explosion, injury, illness, and contamination of personnel and the environment. Fire safety
precautions and spill control containment measures must be strictly observed. Failure to follow
this warning may result in injury or death to personnel.
FDS must be properly grounded prior to connection of any fuel hoses or to electrical supply.
Failure to properly ground the FDS may result in injury or death to personnel.
The FDS has three drain ports located at the pump, the ilter, and the fuel nozzle. This work package discusses
how to drain the suction hose, pump, ilter shell, discharge hose and fuel nozzle. It also discusses how to drain the
complete system.
Drain Suction Hose
1.  Position a drain pan (Figure 22, Item 2) beneath the pump inlet coupling (Figure 22, Item 1). The drain pan
should be of suficient size to hold between 3 to 5 gallons of fuel.
2.  Ensure the valve at the fuel source is turned off.
000514