TM 5-4320-305-24
2-18. REPLACE/REPAIR SUCTION ASSEMBLY, STRAINER ASSEMBLY,
AND GATE VALVE (Continued)
ASSEMBLY:
1 Install preformed packing (10) and strainer (9) in
strainer body (5).
2 Install strainer clamp (8) on strainer body (5) with
locking lever (6) and lever bolt (7).
3 Tighten lever bolt (7) and lock locking lever (6).
4 Install 90-degree elbow (4) and reducer (3) on
strainer body (5).
5 Install suction pressure hose (2). Tighten hose clamp
(1) securely.
6 Install new gasket (15) and spool flange (14) on strainer body (16) studs with nuts (12) and lockwashers (13). Tighten
nuts.
7 Install new gasket (11) and gate valve (1U) on spool flange (14) with cap screws (7), lockwashers (9), and nuts (8).
Tighten cap screws.
8 Install new gasket (6) and flange (5) on gate valve (10) with cap screws (1), lockwashers (2), and hex nuts (3). Tighten
cap screws (1).
2-74
|