TM 10-6630-240-12&P
TM 01461B-12&P/1
2-8. METHOD FOR UNDISSOLVED WATER TESTING.
Collect a 500 milliliter (17.0 ounce) sample of fuel. Pass the fuel through the sampler with the free-water test pad
contained within the stainless steel monitor. Remove the free water test pad from the monitor and blot dry between
paper towels. Insert free-water test pad into Aqua-Glo Water Detector and record ppm of water.
2-9. CALIBRATING THE AQUA-GLO WATER DETECTOR.
NOTE
To insure accurate undissolved water detection, calibrate the AQUA-GLO Water Detector
before each daily use and after every hour of use.
a.
Turn on the water detector (1), setting the indicator switch (2) to the appropriate power source: set to either AC
(power cord (3)), internal, or external battery. (figure 2-17)
Figure 2-17
2-13
|