Use the gravity calculator (1) attached to the test kit placard, to determine the correct API: select the appropriate
type of fuel being tested (2) and turn the computer slide to match the recorded API gravity with the recorded temperature.
Read and record the corrected gravity, temperature, and relative density indicated at the 60° (3) mark on the computer
scale . Refer to the example shown on the gravity calculator as well. Compare the readings to the established site
standards and record the test results. Determine if the fuel sample satisfies specified site standards.(figure 2-16)
Figure 2-16