Connect the Sampler Valve Hose Assembly(l) to the Quick-Release Valve (2). The three way valve (3) must be
in the off position before attaching the Sampler to the hose assembly. Remove protective cap (4) from inlet hose nipple
(5) and plug (6) from the quick-release valve collar (7). Insert sampler hose nipple (5) into quick-release collar (7).
(figure 2-5)
Figure 2-5
WARNING
The Sampler Valve Hose Assembly must be properly grounded to avoid possible fire or
explosion from static electrical charges. An electrical continuity test of the ground hook-up
should be performed prior to test to assure conductance of electrical charges from system to
ground.
f.
Attach one end of ground wire (1) on any metal part of the hose assembly (2) and the other end to a ground.
(figure 2-6)
Figure 2-6