4. Post signs indicating where to seek help in case of an emergency.
Siting Requirements
The site area must be bermed to stop the flow of fuel in case of rupture or leakage. An erected dyke
should have the following characteristics:
1. At least a 13 foot (3.05 m) working area between the tank and walls.
2. Walls 5 feet, 6 inches (1.7 m) high (high enough for the internal volume to be 1-1/2 times greater than
the volume of the tank).
3. Walls protected against erosion with sod or stone. Wall heights should not fall below 4 feet, 6 inches
(1.4 m).
4. A drain pipe and valve at the low end of the site to remove accumulated rain water. The drain should
normally be kept closed. It can be opened as needed.
95' (29 m)
MIN
13'-0" (3.05 m)
VENT
ALL AROUND
FILL/DISCHARGE
CONNECTION
TANK
BERM
1-1/2' (0.47 m)
1' (0.31 m)
5'-6" (1.7 m)
EMPTY
TANK
PLUG OR VALVE
GRADE
MAX SLOPE 3' (7.62 m)
3" (7.62 cm) DEEP SUMP
DRAIN PIPE
0005 00-2
|