TM 10-5430-239-12&P
OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANK, PETROLEUM, 5,000 BARREL
OPERATION UNDER USUAL CONDITIONS
SITING REQUIREMENTS
For proper tank function, an appropriate site must be chosen.
Dimensions
1. Select or grade a level area of at least 95 x 95 feet (29 x 29 m). This will provide the desired 13-foot
(4 m) perimeter around the empty flat tank.
NOTE
Berm liner must be used.
2. For tank operation, the tank bed area will have a slope of 3 inches (7.62 cm) in 100 feet (30.5 m). Do
not exceed 12 inches (30.5 cm) in 100 feet (30.5 m). The site must not be subject to flooding or high
water.
CAUTION
Clear the site of all sharp objects that might puncture or scuff the tank.
3. If the site selected has a slight slope, place one of the tank sides with a drain fitting and
filler/discharge fitting at the lowest end.
Final Site Preparation
WARNING
FLAMMABLE FUEL. Do not allow smoking within 100 feet (30.50 meters)
of the storage area. Post NO SMOKING signs around the area. Avoid
getting fuel on the body or clothing. If clothing becomes saturated with
fuel, remove the clothing immediately and wash body with hot soapy water
and soak clothing in soapy water. Avoid spillage of fuel. When spillage
occurs, cover the affected area with dry soil to reduce its rate of vaporization.
Be certain a suitable fire extinguisher is present and that it is properly
charged and positioned so as to be readily available in case of fire. Death or
serious injury may result if personnel fail to strictly observe safety precautions.
CAUTION
Electrical equipment used within 50 feet (15.25 m) of the tank should be
approved for use in Class 1, Group D, Division 1, hazardous locations as
defined by the National Electrical Code.
1. Clear the site area within 100 feet (30.5 m) of the tank of all dry grass, brush and weeds. Remove all
spark-producing equipment or devices from the cleared area. Post signs stating "FLAMMABLE
LIQUID NO SMOKING OR OPEN FLAME WITHIN 100 FEET OF TANK."
2. Have fire extinguishing equipment on hand. Equipment should include a quick-smothering type of
extinguishing agent, such as carbon dioxide or dry chemical, or a permanent type of extinguishing
agent, such as foam. Locate equipment approximately 50 feet (15.25 m) from tank.
3. Secure area by fencing or other means to prevent access by unauthorized personnel.
0005 00-1
|