OPERATOR\CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)
OPERATOR\CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)

OPERATOR AND FIELD MAINTENANCE MANUAL FOR TANK UNIT, FUEL DISPENSING, TRAILER MOUNTING: FUEL DISTRIBUTION SYSTEM
Page Navigation
  74    75    76    77    78  79  80    81    82    83    84  
img
0014
TM 10-4930-369-13&P
EQUIPMENT
ITEM TO BE
ITEM
INTERVAL
NOT READY/
CHECKED OR
NO.
PROCEDURE
AVAILABLE IF:
SERVICED
Figure 8. Flow Meter.
2.
Check that low meter does not have a
Damage
crack or other damage to display.
prevents the
low meter
from operating
correctly.
2
During
Pipes or pipe
Piping System
Check pipes and pipe joints for leaks or
joints are
damage.
damaged or
leaking.
Parts damaged or
3
During
Grounding Reel
defective.
Figure 9. Grounding Reel.
Check grounding reel (Figure 4, Item 3) for:
1. Damaged cables (Figure 4, Item 1) and
ground clip (Figure 4, Item 2).
2. Broken or defective mechanical parts.
3. All component parts are clean.
4. Ground clips clamps securely (Figure 4
Item 2).
5. Cable (Figure 4, Item 1) extends, locks
and retracts on reel (Figure 4, Item 3)
properly.
Needle is in the
4
During
1.  Check during normal operation of FDS
Differential
red zone.
(while pumping fuel), the differential
Pressure
pressure gauge (Figure 8, Item 1)
Gauge
located on the ilter head as follows:
When needle is in the green zone of
the differential pressure gauge during
normal low, the differential pressure
gauge does not need to be replaced.
When the needle is in the red zone, the
ilter cartridge is not operating normally.