TM 10-4930-241-13
2-18. OPERATING PROCEDURES - CONT.
(f)
When fueling operation is completed, shutdown 600 GPM pump.
(g)
Close all valves.
(8)
Refuel Mode - Fuel Tank Bypass. Refer to figure 2-38.
WARNING
Do not touch surfaces with bare skin. Bare skin will freeze to metal
surfaces in subzero temperatures. Always wear arctic mittens when
handling components.
(a)
Connect valve section (1) to supply tanker and open valve.
(b)
Ensure valves (2 and 3) are closed.
(c)
Ensure valves (4 and 5) are open.
(d)
Ensure valves (6 thru 9) are closed.
(e)
Open valves (10 thru 14).
(f)
Ensure valve (15) is closed.
(g)
Start and operate primary and secondary 600 GPM pumps (16 and 17).
(h)
When operation is complete, shut down 600 GPM pumps (16 and 17).
(i)
Close all valves.
Figure 2-38. Refuel Mode - Fuel Tank Bypass.
2-85
|