TM 10-4930-241-13
2-18. OPERATING PROCEDURES - CONT.
(9)
Refuel Mode - Fuel Tank and Secondary Pump Bypass. Refer to figure 2-39.
WARNING
Do not touch surfaces with bare skin. Bare skin will freeze to metal
surfaces in subzero temperatures. Always wear arctic mittens when
handling components.
(a) Connect valve section (1) to supply tanker and open valve.
(b) Ensure valves (2 and 3) are closed.
(c) Open valves (4 and 5).
(d) Ensure valves (6 thru 8) are closed.
(e) Open valves (9 thru 11).
(f)
Ensure valve (12) is closed.
(g) Open valves (13 and 14).
(h) Start and operate primary 600 GPM pump (15).
(i)
When operation is complete shut down 600 GPM pump (15)
(j)
Close all valves.
2-86
|