TM 10-4930-229-12&P
4-19. Adapter, Water Detector Kit.
This task covers:
a. Repair
b. Replace
INITIAL SETUP
Tools:
General Safety Instructions:
Tool Kit, General Mechanics, Item 1, Section III,
Appendix B
l
Materials/Parts:
Cleaning Solvent, Item 4, Appendix E
Rags, Wiping, Item 5, Appendix E
l
Gaskets, P/N MS27030-6, Appendix F
Sealing Compound, Item 3, Appendix E
Equipment Conditions:
FARE shutdown, para 2-12.
WARNING
Do not smoke or use an open flame in the
vicinity of the FARE, failure to comply may
result in personnel injury.
Drain any fuel into suitable container. Clean up
any fuel spills to prevent fire or environmental
hazard.
a. Repair. (figure 4-13)
(1) Disassembly.
(a) Inspect adapter for leaks, ease of operation, and missing or damaged parts.
WARNING
Cleaning solvent, Federal Specification PD-680, is toxic and flammable.
Use only in a well-ventilated area. Avoid prolonged breathing of fumes.
Keep solvent away from flames. Do not use in excessive amounts.
Avoid skin contact.
(b) Clean adapter with cleaning solvent and allow to dry.
(c) Pull upon camlock levers (1) and remove dust plug (2) and gasket (3). Discard gasket.
(d) Pull upon camlock levers (4) and remove dust cap (5) and gasket (6). Discard gasket.
(e) Remove probe assembly (7) from nipple (10).
(f) Remove coupling half (8) and coupling half (9) from nipple (10).
(g) Remove sealing compound from threads.
(h) Replace any parts found to be defective with new parts from stock.
4-30
|