TMS-4930-235-13&P
(31) If removed, install retaining ring (7) on end of indicator shaft (6).
(32) Slide flat washer (8) and spring (5) over indicator shaft (6) and against retaining ring (7).
(33) Insert indicator shaft (6) through center hole of end cap (3).
NOTE
Painted groove on indicator shaft must extend through back of end cap.
(34) Install end cap (3) as follows:
(a) Push indicator shaft (6) through inside of end cap (3) and hold end of indicator shaft (6) against
outside of end cap (3).
(b) Align end cap (3) lugs with nozzle body (47) and press down to compress spring (4). Hold end cap
(3) against nozzle body (47).
(c) Release indicator shaft (6).
(d) Thread capscrews (2) into nozzle body (47) and tighten to a torque of 10-15 ft-lbs (14-21 Nm).
(35) Remove nozzle subassembly (12, Figure 5-1) from vise.
(36) Install o-ring (10) and strainer (9) in strainer housing (11).
(37) Thread strainer body (8) and coupling (7) into strainer housing (11). Hand-tighten only.
(38) If coupling (7) was removed from strainer body (8) install as follows:
(a) Using a brass brush, clean threads to remove old thread sealing compound.
(b) Apply a light, even coat of thread sealing compound to threads of coupling (7).
CAUTION
Do not over tighten strainer body. Failure to comply can result in damage to strainer body.
(c) Thread coupling (7) into strainer body (8) until one to three threads are exposed. Wipe off excess
thread sealing compound.
NOTE
Final assembly of nozzle is done after testing.
5-21
|