TM 5-4930-234-13&P
17.
Wipe exterior of nozzle (13) and cables with a clean, lint-free cloth to remove dust, dirt, moisture, or fuel.
Do not leave nozzle laying on ground. Failure to comply can result in damage to nozzle.
18.
Place nozzle (13) in a storage container away from aircraft.
2-9.
DISCONNECTION OF NOZZLE, MODEL AE83501R.
NOTE
Have a suitable container available to catch any fuel spillage.
1.
Turn handle (5) on fuel hose coupling to NO FLOW position.
2.
Pull ring (3) on coupling (2). Turn nozzle (11) clockwise and remove from fuel hose (4). Release ring (3).
3.
Install dust cap (1) on coupling (2). Turn dust cap (1) clockwise to lock in place.
Section IV. OPERATION UNDER UNUSUAL CONDITIONS
2-10.
OPERATION IN UNUSUAL CONDITIONS. The operating instructions for usual conditions are acceptable.
Operators must take special care in the following areas.
a.
Exterior Cleanliness. Wipe the nozzle, dust caps, dust plugs, and cables with a clean, lint-free cloth to
remove dust, dirt, fuel, moisture, snow, or mud. Moisture, snow, and mud can clog or freeze in pullback sleeve and/or
handle. Never store nozzle if dirty or wet.
b.
Dust Caps and Dust Plugs. When not in use, keep dust caps and dust plugs installed. Dust, dirt, moisture,
or mud can contaminate or damage internal seals. Never install dust caps or dust plugs when dirty or wet.
c.
Storage. When not in use, keep nozzle stored in an area that will protect it from extreme temperatures, dust,
dirt, mud, and physical damage.
2-9/(2-10 Blank)
|