TM 07661B-14/1
APPENDIX A
Figure A 3-14. Hose Reel Replacement - Skid
bolts (6), flat washers (7), lockwashers (8), and nuts (9) to fasten hose reel to mounting frame, figure 3-14.
(2)
Connect AFFF discharge hose (2) and elbow (3) to swivel joint (4) on right side of hose reel, figure 3-14.
Use procedures in NOTE, paragraph 3-14c to seal pipe connections against leakage. Connect discharge hose to tank
piping at nipple (1).
(3)
Connect dry chemical hose (3, figure 3-7) and elbow to swivel joint (4) on right side of hose reel, figure 3-
14. Use procedures in NOTE, paragraph 3-14c to seal pipe connections against leakage. Connect the discharge hose to
dry chemical tank discharge plumbing at nipple (4) figure 3-7).
(4)
Install twin handline assembly (5, figure 3-14) paragraph 3-23d.
(5)
Ensure that twin-agent nozzles are connected and closed. Put valves in normal operating position.
(6)
Pressurize systems and check for leaks, paragraphs 3-13 and 3-14.
(7)
Return fire extinguisher to standby status, paragraph 3-10.