TM 5-3825-220-13&P
6-4.3 50,000 Gal. Fabric Collapsible Tanks and Appurtenances
a.
Refer to the technical manuals noted in para. 6-1.4.
b.
It is recommended that the tank(s) be removed from service, action be taken to determine the cause, and
corrective maintenance action be taken in accordance with the technical manual referenced above whenever the
following occur:
1. Fuel inside the berm.
2. Tank top not laying essentially flat at the fuel level.
3. Serious scratch or scoring on the tank surface
4. Pump cannot take suction off the tank
5. Fuel not entering the tank as intended
6. Leaking tank valves
7. Leaking hoselines to or from the tank
6-4.4 Filter-Separator (GFE)
a.
Refer to the technical manual noted in para. 6-1.5.
b.
It is recommended that a filter-separator be removed from service, action be taken to determine the cause, and
corrective maintenance action be taken in accordance with the technical manual referenced above whenever the
following occur:
1. Excessive or premature pressure drop
2. Leaking head flange joint
3. Leakage of any kind
4. Excessive or premature water carryover as evidenced by sample from the water detector kit adaptor
5. Rattling nozzle when flowing
6-4.5 Flood Light Set (GFE)
a.
Refer to the technical manuals noted in para. 6-1.6.
b.
It is recommended that the tank(s) be removed from service, action be taken to determine the cause, and
corrective maintenance action be taken in accordance with the technical manual referenced above whenever the
following occur:
1. No power generated to lighting unit
2. Lighting tower swaying or offset
3. Excessive engine noise or vibration
4. Electrical shock when touching
5. Electrical arcing anywhere
6. Fuel leakage
6-4.6 Wheel-Mounted Dry Chemical/AFFF Fire Extinguishers
a.
Detailed instructions on the maintenance of the wheel-mounted dry chemical/AFFF fire extinguishers are in the
Marine Corps technical manual TM 076618-14/1 contained in this manual under Appendix A.
6-15
|