4-16 Fuel Transfers - Cont'd.
1.
Connect the supply tanker-truck (or trucks) to the couplings outboard of VI TJ (or V2TJ, V3TJ, V4TJ).
2.
Open V5TJ (or V6TJ), V7TJ, V8TJ, V 1OTJ and V13TJ.
3.
Start pump P1 TJ and open V9TJ. Pressurize and feed the switching manifold.
4.
When the transfer is complete, shut down the pump PITJ and close all valves opened above. Disconnect the
tanker-truck(s).
WARNING
TANKER TRUCK MOVEMENT
Do not allow truck to move away without disconnecting the hoseline. A spill could result.
d.
Transfer Fuel from Switching Manifold to Secondary Module Tanks
Fuel is transferred from the switching manifold to secondary module tanks as follows:
1.
Reset meter MS1J to zero or record the reading.
2.
Open valves in the hoseline route to tank.
a)
ToT1J. OpenV1J,V2J,V3J,V4J andV5J.
b)
To T2J. Open V1J, V2J, V3J, V4J and V8J.
c)
To T3J. Open V1J, V2J, V19J, V20J and V21J.
d)
To T4J. Open v1j, V2J,V19J, V2OJ and V24J.
3.
Transfers may be made to two to four tanks simultaneously if desired, however, the quantity to a specific tank
will not be recorded by meter.
4.
If transferring to more than one tank, the flow to each tank will not necessarily be equal. Close the valves to a
particular tank when the tank top touches the range pole cord.
5.
If transferring to a single tank and a continuing transfer to another tank is desired, first open the valves in the
route to the next tank and then close the valve in the route to the full tank. Record the meter reading at the time of shift
and this can be used to determine the quantity transferred to the first tank.
6.
When the transfer is complete to all tanks, close valve V1J and record the meter reading.
7.
Close all valves opened in the transfer process.
4-35
|