3-22.2
Installation. - Cont'd . Refer to figure 2-64.
d.
Connect coupling reducer (24) and coupling adapter (3) to 4-inch Y assembly (9).
e.
Connect 6-inch discharge hose (40) between primary module cross assembly and Y assembly (9).
f.
Connect 4-inch coupling reducer (23) and 6-inch coupling adapter (22) to 4-inch Y assembly (7).
g.
Install 4-inch dispensing hose (5) between gate valves (6), mounted on filter separators (8), and 4-inch Y
assembly (7).
h.
Connect 6-inch discharge hose (4) between Y assembly (7) and inlet side of meter strainer (29).
i.
Connect coupling reducers (25) and 4-inch gate valves (6) to reducer tees (3). Position assembly units as shown.
j.
Connect 6-inch gate valve (26) to reducer tee (3).
k.
Install 6-inch discharge hose from outlet port of meter strainer (29) to 6-inch gate valve (26).
I.
Connect 4-inch ball valves (10) and reducer couplings (28) to ends of 4-inch dispensing hoses (5). Connect
other ends of hoses to 4-inch gate valves (6).
m.
Connect 6-inch coupling adapter (13), 6-inch coupling reducer (24), and 4-inch reducing valve assembly (2) to
reducer tee (3).
n.
Connect 1.5-inch dispensing hoses (14) to reducer tee assemblies (15S). Connect 1.5-inch ball valves (12) to
hoses.
o.
Connect 6-inch discharge hoses (4) between reducer tees (3).
p.
Connect 3-inch reducer valve assembly (16) to reducer tee (17).
q.
Connect 1-inch coupling adapters (19) to 1-inch dispensing hose assemblies (18). Install 2-inch nozzles (20) on
coupling adapters.
r.
Connect 3-inch dispensing hose (1) between 4-inch valve assembly (2) and reducer tee assemblies (15).
s.
Connect 3-inch reducer valve assembly (16) to reducer tee (17) and 3-inch dispensing hose (1).
t.
Install 2-inch dispensing hoses (21) between reducer tees(17).
u.
Inspect all connections to verify correct installation of flanges, coupling gaskets and clamps, and security of cam
lock devices.
3-18
|