3-13 Install 600 Gpm Hoseline Pumps
Four (4) per fuel unit/twelve (12) per TPT
One (1) per tanker-truck receipt manifold/three (3) per TPT
3-13.1
Install, service, and prepare for operation in accordance with the instruction in the technical manual
published by Peabody Barnes, Inc. for their Model US612-ACD-1 and overpacked with each pump.
3-13.2
For general information, refer to para.'s 2-4.3, 3-7.1,3-7.2 and Fig. 2-13.
3-13.3
Approximate erection weight 3380 Ibs. ea.
WARNING
Ground the pumps at time of installation.
WARNING NOTE
Observe all warnings and cautions noted in the Peabody Barnes, Inc. technical manual.
CAUTION
Install pumps as far away from the tanks as possible without deforming tank top or causing
long unsupported lengths of suction hose. The suction hose should lay on the ground
without strain on the tank or pump. Pump engines and exhaust fumes are hot and distance
from the tank will enhance safety.
3-14 Install 350 Gpm Transfer Pump
One (1) per contaminated fuel module/one per TPT 3-14.1 Install, service, and prepare for operation in accordance with
Department of the Army technical manual TM 5-4320-226-14.
3-14.2
General information on this pump is in para. 2-4.4 and fig. 2-16 in this manual. See final field plot plan for
location.
3-14.3
Erection weight is 21401bs.
WARNING NOTE
Observe all warnings and cautions stated in TM 5-4320-226-14.
WARNING
Ground pumps at time of installation.
CAUTION
Install pump as far away from the tanks it serves as possible without bridging the suction
hose or deforming the tank top. Pump engine and exhaust fumes are hot and distance from
tanks enhances safety.
3-10
|