TM 10-6630-240-12&P
TM 01461B-12&P/1
Section III. OPERATION UNDER USUAL CONDITIONS
2-5. ASSEMBLY AND PREPARATION FOR USE.
a.
Unlatch the case and open to gain access to the equipment and instructions.
b.
Depending on the type of petroleum test to be performed, various pieces of equipment will be removed from the
case to accomplish the testing. See instructions placards for equipment utilized for each test.
c.
Using the eight-inch adjustable wrench, attach the quick-release valve (1) to the system fitting (2) (this will vary
with the type of equipment you are using, however, attach the valve in a horizontal position on the system or at the top of
the system to allow for proper flushing). Keep the valve plug (3) in its fitting when valve is not in use.(Figure 2.1).
Figure 2-1
2-26. OPERATING INSTRUCTIONS FOR PARTICULATE CONTAMINANT TEST.
a.
With the quick - release valve in place, you are ready to select a monitor. Use contamination monitors (blue and
red protective plugs) for color comparator testing and matched weight monitors (yellow and red protective plugs) for
gravimetric testing. Remove the plugs from the monitor; remove the bottom (red) plug from the monitor first, followed by
the top (blue or yellow) plug. Keep plugs in a safe place for replacement on monitors when test is completed.
b.
Unscrew the sampler cover (1) from the sampler base (2) and insert the monitor (3) spoke-side down into the
base. Insert the sampler base (2) with the monitor (3) in place into the sampler cover (2) and screw the two pieces(l & 2)
together to a snug hand tightness. (Figure 2.2).
Figure 2-2
2-3
|