TM 10-5430-242-12&P
0011 00
0011 00-1/ 2 blank
OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANKS, FUEL STORAGE, 3,000,
10,000, 20,000, AND 50,000 GALLON
FILLER/DISCHARGE GATE VALVE (GTA MODEL), HOSE ASSEMBLY
COUPLING AND DUST CAP GASKET
REPLACEMENT
INITIAL SETUP
Mandatory Replacement Parts
Gasket
(Item 1, WP 0044 00)
REMOVAL
The filler/discharge hose is fitted with a female quick-disconnect coupling on one end and a male quick-
disconnect adapter on the other end.
1. Pull two cam-lever arms (1) outward on female quick-disconnect coupling (2), and hose assembly
coupling (3). Disconnect hose assembly (4) from filler/discharge valve assembly (5)
2. Remove coupling gasket (6) from inside female quick-disconnect coupling (2). Discard gasket (6).
3. Remove hose assembly gasket (7) from inside hose coupling (8). Discard gasket (7).
4. Remove dust cap (9). Remove gasket (10) from dust cap (9). Discard gasket (10).
INSTALLATION
1. Install new gasket (10) in dust cap (9). Install dust cap (9).
2. Install new hose assembly gasket (7) inside hose coupling (8).
3. Install new coupling gasket (6) inside female quick-disconnect coupling (2).
4. Connect hose assembly (4) to filler/discharge valve assembly (5).
5. Push in on cam-lever arms (1) to lock hose assembly (4) in place.
END OF WORK PACKAGE
1
9
2
4
5
6
7
8
10
3
|