TM 10-5430-242-12&P
0032 00
0032 00-1
OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANKS, FUEL STORAGE,
10,000 AND 20,000 GALLON
BERM LINER DRAIN FITTING ASSEMBLY (RELIANCE MODEL)
SERVICE AND REPAIR
INITIAL SETUP
Tools
Equipment Condition
Tool Kit General Mechanics
Berm liner drain hose assembly removed
(Item 1, WP 0036 00
(WP 0031 00)
Torque Wrench (ft-lb)
(Item 3, WP 0036 00)
Mandatory Replacement Parts
Gasket
Materials/Parts
(Item 3, WP 0044 00)
Anti-seize Tape
O-ring
(Item 1, WP 0042 00)
(Item 9, WP 0044 00)
Detergent
(Item 6, WP 0042 00)
Dry Cleaning Solvent
(Item 7, WP 0042 00)
Rags, Wiping
(Item 2, WP 0042 00)
Sealing Compound
(Item 9, WP 0042 00)
Silicone Compound
(Item 10, WP 0042 00)
DISASSEMBLY
1. Disconnect chain assembly (1) from male disconnect coupling (2) and dust cap (3).
2. Remove dust cap (3) from male disconnect coupling (2) by pulling outward on cam-lever arms (4) and
lifting dust cap (3) from male disconnect coupling (2). Remove and discard gasket (5) from dust cap
(3).
3. Unthread male disconnect coupling (2) from drain cover plate (6).
4. Remove eight screws (7) and washers (8) from drain cover plate (6) and berm liner (9).
5. Remove drain cover plate (6), o-ring (10), and screen (11).
6. Discard o-ring (10).
SERVICE
WARNING
Dry cleaning solvent, A-A-59601, used to clean parts, is potentially dangerous to
personnel and property. It produces toxic and flammable fumes. Use only in well
ventilated areas. Avoid repeated and prolonged skin contact. Do not use solvent
near an open flame or near excessive heat. The flash point of the solvent is 100F
to 130F (38 C to 59 C).
|