OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANK, PETROLEUM, 5,000 BARREL
DRAIN GATE VALVE (TANK MODEL PD5430-0001)
REPAIR
INITIAL SETUP
Tools
Mandatory Replacement Parts
Tool Kit, General Mechanics
Gasket
(Item 1, WP 0034 00)
(Item 6, WP 0044 00)
Materials/Parts
Equipment Condition
Sealing Compound
Drain gate valve removed
(Item 9, WP 0041 00)
Antiseize Tape
(Item 2, WP 0041 00)
WARNING
FLAMMABLE FUEL. Do not allow smoking within 100 feet (30.50 meters)
of the storage area. Post NO SMOKING signs around the area. Avoid
getting fuel on the body or clothing. If clothing becomes saturated with
fuel, remove the clothing immediately and wash body with hot soapy water
and soak clothing in soapy water. Avoid spillage of fuel. When spillage
occurs, cover the affected area with dry soil to reduce its rate of vaporization.
Be certain a suitable fire extinguisher is present and that it is properly
charged and positioned so as to be readily available in case of fire. Death or
serious injury may result if personnel fail to strictly observe safety precautions.
DISASSEMBLY
1. Remove nut (1) from hand-wheel (2). Remove hand-wheel (2).
2. Turn couplings (3, 4) counterclockwise and remove couplings (3, 4) from valve (5).
3. Pull outward on two cam-lever arms (6) and remove dust cap (7) from coupling (3). Remove gasket
(8) from inside dust cap (7). Discard gasket (8).
4. Inspect parts for damage, dents and wear. Replace as required.
ASSEMBLY
1. Apply sealing compound on threads of couplings (3, 4) or wrap threads with antiseize tape. Engage
threads of couplings (3, 4) with threads of valve (5) and turn clockwise until tight.
2. Position new gasket (8) inside dust cap (7). Insert dust cap (7) over coupling (3). Push in cam-lever
arms (6) to lock dust cap (7) on coupling (3).
3. Install hand-wheel (2) on valve (5) with nut (1).
4. Install drain gate valve (WP 0023 00).