TM 10-5430-239-12&P
0020 00
4. Remove o-ring (9) from inside o-ring groove in tank fitting (8). Discard o-ring (9).
5. Remove twelve screws (10) and washers (11) and remove flanged adapter (3), two gaskets (12) and
suction stub (13) from closure plate (7). Discard gaskets (12).
6. Remove gasket (14) from inside of dust cap (15). Discard gasket (14).
2
1
10
11
4
12
3
15
5
14
6
7
13
12
9
8
SERVICE
WARNING
Dry cleaning solvent A-A-59601, used to clean parts, is potentially dangerous
to personnel and property. It produces toxic and flammable fumes. Use only
in well-ventilated areas. Avoid repeated and prolonged skin contact.
Do not use near an open flame or excessive heat. The flash point of solvent is
100F to 138F (38C to 59C).
1. Clean all parts with dry cleaning solvent and dry thoroughly.
2. Clean out o-ring grooves thoroughly with cleaning compound and hot water.
3. Inspect all mechanical parts for cracks, dents, breaks or wear. Replace or repair if unserviceable.
0020 00-2
|