TM 10-5430-239-12&P
0017 00
Table 1. Unit Preventive Maintenance Checks and Services
for Fuel Storage Tank (continued).
EQUIPMENT
ITEM
MAN-
ITEM TO BE CHECKED
INTERVAL
PROCEDURE
NOT READY/
NO.
HOUR
OR SERVICED
AVAILABLE IF:
Drain Fitting
15
During
Check immediate area for
Drain plug, drain
Assembly (7)
evidence of leaks. Check
hose or drain
the drain plug, drain hose
ball valve are
or drain valve for damaged
missing,
or missing parts.
improperly
connected or
damaged.
Berm Liner Drain Fitting
16
During
Check immediate area for
Drain plug, drain
Assembly (8)
evidence of leaks. Check
hose or drain
the drain plug, drain hose
ball valve are
or drain ball valve for
missing,
damaged or missing parts.
improperly
connected,
damaged or
leaks.
17
After
Tank (1)
Inspect for tears,
Tank has tears
punctures or leaks.
or punctures that
cannot be
repaired.
18
After
Filler/Discharge
Check for bent or binding
Stem or hand-
Gate Valve (2)
stem or broken hand-
wheel is
wheel.
damaged or
missing.
19
After
Drain Ball Valve (3)
Check for bent or binding
Stem or handle
stem or broken handle.
is damaged or
missing.
20
After
Drain Gate Valve (4)
Check for bent or binding
Stem or hand-
stem or broken hand-
wheel is
wheel.
damaged or
missing.
21
After
Vent and Pipe
Check for evidence of
Evidence of
Assembly (5)
leakage, damage or
leakage. Relief
missing parts. Check the
cap or flame
relief cap for cleanliness
arrestor is
and freedom of operation.
damaged or
Check if the flame
missing. Relief
arrestor, relief cap gasket,
cap gasket, flat
flat rubber gasket or cam-
rubber gasket or
lever arms are damaged
cam-lever arms
or missing.
are damaged or
missing.
0017 00-6
|