INITIAL SETUP
Mandatory Replacement Parts
Gasket
(Item 5, WP 0044 00)
WARNING
FLAMMABLE FUEL. Do not allow smoking within 100 feet (30.50 meters)
of the storage area. Post NO SMOKING signs around the area. Avoid
getting fuel on the body or clothing. If clothing becomes saturated with
fuel, remove the clothing immediately and wash body with hot soapy water
and soak clothing in soapy water. Avoid spillage of fuel. When spillage
occurs, cover the affected area with dry soil to reduce its rate of vaporization.
Be certain a suitable fire extinguisher is present and that it is properly
charged and positioned so as to be readily available in case of fire. Death or
serious injury may result if personnel fail to strictly observe safety precautions.
REMOVAL
The filler/discharge hose is fitted with a female quick-disconnect coupling on one end and a male quick-
disconnect adapter on the other end.
1. Pull two cam-lever arms (1) outward on female quick-disconnect coupling (2), and hose assembly
coupling (3). Disconnect hose assembly (4) from filler/discharge valve assembly (5).
2. Remove coupling gasket (6) from inside female quick-disconnect coupling (2). Discard gasket (6).
3. Remove hose assembly gasket (7) from inside hose coupling (8). Discard gasket (7).
4. Remove dust cap (9). Remove gasket (10) from dust cap (9). Discard gasket (10).
2
8
9
5
10
7
1
6
3
4