|
|
TM 10-5430-239-12&P
OPERATOR AND UNIT MAINTENANCE
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANK, PETROLEUM, 5,000 BARREL
UNIT TROUBLESHOOTING PROCEDURES
INTRODUCTION TO UNIT TROUBLESHOOTING
The Unit Troubleshooting Procedures chapter lists common malfunctions that may be found during the
operation or maintenance of the collapsible fabric petroleum tank assembly or its components. Perform
the tests/inspections and corrective actions in the order listed in the table.
This manual cannot list all malfunctions that may occur, nor all tests or inspections and corrective actions.
If a malfunction is not listed or is not corrected by listed corrective actions, notify supervisor.
TROUBLESHOOTING PROCEDURE
WARNING
FLAMMABLE FUEL. Do not allow smoking within 100 feet (30.50 meters)
of the storage area. Post NO SMOKING signs around the area. Avoid
getting fuel on the body or clothing. If clothing becomes saturated with
fuel, remove the clothing immediately and wash body with hot soapy water
and soak clothing in soapy water. Avoid spillage of fuel. When spillage
occurs, cover the affected area with dry soil to reduce its rate of vaporization.
Be certain a suitable fire extinguisher is present and that it is properly
charged and positioned so as to be readily available in case of fire. Death or
serious injury may result if personnel fail to strictly observe safety precautions.
VENT ASSEMBLY
SYMPTOM
Vent assembly leaks.
MALFUNCTION
Check o-ring between flanged adapter and tank for nicks or distortion.
CORRECTIVE ACTION
Replace o-ring (WP 0019 00).
Check vent stand pipe for cracks or damage.
CORRECTIVE ACTION
Replace vent stand pipe (WP 0019 00).
Check coupling half for breaks, cracks, damaged cam-lever arms, or damaged
and missing gasket.
CORRECTIVE ACTION
Replace gasket (WP 0019 00).
Check for loose or missing hexagon head bolts.
CORRECTIVE ACTION
Tighten or replace bolts (WP 0019 00).
0008 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |