NOTE
If the tank begins to roll or creep when being filled, place sandbags along the
lower edge of the tank to prevent further creeping or rolling.
4. Activate fuel source. Fill tank. Tank is filled to capacity when it reaches a height of 6 feet, 8 inches
(2.06 meters). For model GTA-210KF, capacity is 6 feet, 0 inches (1.8 meters). Do not overfill tank.
5. When tank is full, stop pumping.
6. Close filler/discharge gate valve.
7. Disconnect fuel source hose from filler/discharge gate valve.
8. Close vent assembly cap.
9. Check tank for leakage. If tank leaks, follow troubleshooting procedures in WP 0007 00.
WARNINGS
FLAMMABLE FUEL. Do not allow smoking within 100 feet (30.50 meters)
of the storage area. Post NO SMOKING signs around the area. Avoid
getting fuel on the body or clothing. If clothing becomes saturated with
fuel, remove the clothing immediately and wash body with hot soapy water
and soak clothing in soapy water. Avoid spillage of fuel. When spillage
occurs, cover the affected area with dry soil to reduce its rate of vaporization.
Be certain a suitable fire extinguisher is present and that it is properly
charged and positioned so as to be readily available in case of fire. Death or
serious injury may result if personnel fail to strictly observe safety precautions.
If fuel spills on or around a tank or within the diked area, shut down any
nearby engine-driven equipment. Do not resume operation until it has been
determined that the vapor concentrations are below the explosive range.
Fuels and fuel sludge can cause injury to skin or eyes.
If fuel or sludge comes into contact with skin, flush with soap and water.
If fuel or sludge comes into contact with eyes, flush with water.
For further information on first aid, refer to FM 4-25.11.
Fumes from stored fuels are hazardous. Do not carry or store anything
edible near tank. Food will absorb vapors. After leaving area, wash before
eating or smoking.
Discharging Fuel
1. Attach line from user's container to gate valve.
2. Open gate valve.
3. Activate pumping source.
4. Monitor metering source.
5. When user's requirement is fulfilled, stop pumping.
6. Close gate valve.
0005 00-14
|