INITIAL SETUP
Tools
Equipment Condition
Tool Kit General Mechanics
Fuel tank drained
(Item 1, WP 0033 00)
Torque Wrench (in-lb)
(Item 2, WP 0033 00)
Materials/Parts
Mandatory Replacement Parts
Dry Cleaning Solvent
Gasket
(Item 4, WP 0040 00)
(Item 2, WP 0042 00)
Rags, Wiping
Gasket Cap
(Item 6, WP 0040 00)
(Item 14, WP 0042 00)
Silicone Compound
O-Ring
(Item 9, WP 0040 00)
(Item 15, WP 0042 00)
Relief Cap Gasket
(Item 16, WP 0042 00)
REMOVAL
1. Remove screws (1) and washers (2) from vent and pipe assembly (3).
2. Lift male-flanged adapter (4) from tank fitting (5).
3. Remove and discard O-ring (6) from packing groove (7) located in tank fitting (5).
DISASSEMBLY
1. Remove female quick-disconnect coupling (8) from male-flanged adapter (4) by pulling outward
on cam-lever arms (9), and lifting female quick-disconnect coupling (8) from male-flanged adapter (4).
2. Remove and discard gasket (10) from female quick-disconnect coupling (8).
3. Rotate vent pipe (11) counterclockwise until the vent pipe threads disengage from female
quick-disconnect coupling (8), and remove female quick-disconnect coupling (8) from vent pipe (11).
4. Rotate relief cap (12) counterclockwise until the relief cap threads disengage from vent pipe (11).
Remove the relief cap (12) from the vent pipe (11).
5. Remove and discard relief cap gasket (13) from inside relief cap (12).
6. Rotate flame arrestor (14) counterclockwise until the flame arrestor threads disengage from relief
cap (12). Remove flame arrestor (14) from relief cap (12).
7. Remove and discard gasket (15) from inside dust cap (16).
8. Remove vent relief cap screw (17), washer (18), and gasket (19) from lever head assembly (20).
Discard gasket (19).