TM 10-5430-238-12&P
OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANKS, FUEL STORAGE, 3,000,
10,000, 20,000, AND 50,000 GALLON
FILLER/DISCHARGE GATE VALVE ASSEMBLY (MODELS WTM3KF,
MIL-T-52983B, PD52983-50, M52983-50, BA92-162, FCE574-81-1-A, SC5430-97CLE01)
SERVICE, REPLACEMENT, REPAIR
INITIAL SETUP
Tools
Equipment Condition
Tool Kit General Mechanics
Fuel tank drained
(Item 1, WP 0033 00)
Torque Wrench (in-lb)
(Item 2, WP 0033 00)
Torque Wrench (ft-lb)
(Item 3, WP 0033 00)
Materials/Parts
Mandatory Replacement Parts
Crocus Cloth
Gasket
(Item 2, WP 0040 00)
(Item 1, WP 0042 00)
Detergent
Gaskets
(Item 3, WP 0040 00)
(Item 3, WP 0042 00)
Dry Cleaning Solvent
Gasket, Valve Bonnet
(Item 4, WP 0040 00)
(Item 5, WP 0042 00)
Grease
Lockwashers
(Item 5, WP 0040 00)
(Item 4, WP 0042 00)
Rags, wiping
Lockwashers
(Item 6, WP 0040 00)
(Item 6, WP 0042 00)
REMOVAL
Hose Assembly, Coupling, and Adapter
1. Remove hose assembly (1) from gate valve assembly (2) by pulling two cam-lever arms (3) outward
on female quick-disconnect coupling (4).
2. Remove hose assembly (1).
3. Remove the chain and dust cap (5) from female quick-disconnect coupling (4), and the chain and dust
plug (6) from male-flanged adapter (7). Remove gasket (8) from male-flanged adapter (7).
4. Remove coupling gasket (9) from inside female quick-disconnect coupling (4).
5. Remove eight hex nuts (10), lockwashers (11), hex-head cap screws (12), and washers (13).
6. Remove female quick-disconnect coupling (4) and flange gasket (14) from face of gate valve (15).
7. Remove eight hex nuts (16), lockwashers (17), hex-head cap screws (18), and washers (19) from the
opposite end of gate valve (15).
8. Remove male-flanged adapter (7) and flange gasket (20).