Check the preformed packing between the closure plate and the tank fitting for
nicks, breaks, and compression.
CORRECTIVE ACTION
Replace the preformed packing. See WP 0027 00.
SYMPTOM
Filler/discharge assembly leaks between the closure plate and flanged adapter.
MALFUNCTION
Check for missing or loose nuts, lockwashers, thread seal washers, and hex
head cap screws.
CORRECTIVE ACTION
Replace missing nuts, lockwashers, thread seal washers, and
hex-head cap screws Torque the fastening hardware to 30 in-lb
(3.41 Nm). See WP 0027 00.
Check the flange gasket for damage or wear.
CORRECTIVE ACTION
Remove the flange adapter from the closure plate and replace
the damaged flange gasket. See WP 0027 00.
SYMPTOM
Filler/discharge assembly leaks through hardware or will not assemble.
MALFUNCTION
Check all filler/discharge fastening hardware for cracks, damages, and wear.
CORRECTIVE ACTION
Replace the fastening hardware as required. Torque the
fastening hardware to 30 in-lb (3.41 Nm). See WP 0027 00.
SYMPTOM
Filler/discharge assembly elbows leak.
MALFUNCTION
Check elbows for cracks, dents, or wear. Check for damaged or missing elbow
gaskets.
CORRECTIVE ACTION
Replace damaged elbows and gaskets. See WP 0027 00.
0008 00-7
|