TM 10-4930-250-13&P
4. Pumpoperatesatlow capacity.
Step 1. Check for blockage.
a.
Disconnect lines from inlet and outlet unisex couplings.
b.
Open coupling valves and visually inspect for blockage. Remove any blockage.
Step 2.
Check for clogged strainer.
a.
Separate pump from inlet reducer.
b.
Remove and clean strainer.
Step 3. Replace pump.
ENGINE
Refer to TM 10-4320-351-14.
FUEL TRANSFER PUMP
Refer to TM 10-4320-351-14.
FILTER-SEPARATOR,
WATER, LIQUID FUEL
Refer to TM 10-4330-237-13&P.
D-1 NOZZLE
Refer to TM 104930-246-13&P.
CCR NOZZLE ASSEMBLY
Refer to TM 10-4930-248-13&P.
4-7
|