Table4-1. Unit LevelPreventiveMaintenanceChecksandServicesforAAFARS
Item Interval
Location
Procedure
Not Fully Mission
No.
Capable If:
Item to
Check/
Service
Fuel fumes are always present in the vicinity
of the
AAFARS. Death or personal injury may result
from the explosion of fuel fumes exposed to an
open flame or spark. Do not permit any smoking,
any open flame, or spark producing equipment
within fifty (50) feet (15.24 m) of the AAFARS.
1
Pumping
Refer to TM 10-4230-351-14.
Assembly
2
D-1 Nozzle
Refer to TM 4930-246-13&P
3
Monthly
All Fuel
Using a multimeter, test fuel hose for broken or disconnected
Hose fails continuity
Hoses
internal ground cable as follows:
test
1. Place multimeter leads against metal surface of both
couplings.
2.
Check for continuity between couplings. Continuity
must exist. If continuity does not exist, hose is defective.