TM 10-4930-247-13&P
Table 2-1. Operator Preventive Maintenance Checks and Services for
Models HTARS100 and HTARS101 - cont.
Item
Location
No.
Interval
Item
Procedure
Not Fully Mission
Check/Service
Capable If:
22
After
CCR Nozzle
Perform "AFTER" PMCS in accordance
with TM10-4930-248-13&P
23
After
Open Port
a. Inspect for cracked nozzle body.
Nozzle body cracked.
Nozzle
b. Inspect for bent or broken control
Control handle
handle.
broken.
c. Inspect for damaged or missing dust cap
or plug.
24
After
Single Point
a. Inspect nozzle for cracks and loose, bent
Nozzle body cracked;
Refueling Nozzle
or broken locking handles.
locking handles
broken.
b. Inspect control lever for cracks.
Control lever cracked.
c. Inspect nozzle collar for rocks or debris
stuck in adapter locking grooves. Clean as
required.
d. Inspect adapter end of nozzle for
Adapter cracked or
excessive wear, cracks or damage.
Damaged.
e. Inspect non-valved dry break couplings
Locking pin stuck;
for broken lock lugs and damaged or
seal damaged or
missing seals.
missing.
f. (Model HTARS101) Inspect strainer
screen for dirt and debris. Clean as
required.
g. (Model HTARS101) Inspect strainer
Screen cut or torn.
screen for cuts and tears.
25
After
Recirculation
a. Inspect nozzle body for cracks and
Nozzle cracked;
Nozzle
loose, bent or broken locking handles.
locking handles
broken.
b. Inspect control lever for cracks.
Control lever cracked
or broken.
Change 4 2-17
|