TM 10-4930-247-13&P
Table 2-1. Operator Preventive Maintenance Checks and Services for
Models HTARS100 and HTARS101 - cont
Item
Location
No.
Interval
Item
Procedure
Not Fully Mission
Check/Service
Capable If:
12
During
CCR Nozzle
Perform "DURING" PMCS in accordance
with TM10-4930-248-13&P
13
During
Open Port
Inspect for leaks at fuel discharge tube,
Any fuel leak.
Nozzle
nozzle body and coupling.
14
During
Single Point
a. Inspect for leaks through end of nozzle
Any fuel leak.
Refueling Nozzle
(discharge end).
b. Inspect nozzle body and coupling for
Any fuel leak.
leaks.
c. (Model HTARS101) Inspect for
Any fuel leak.
leakage at pressure regulator breather.
15
During
Recirculation
a. Inspect for leaks through end of nozzle
Any fuel leak.
Nozzle
(discharge end).
b. Inspect for leaks between inlet adapter
Any fuel leak.
and nozzle body.
c. Inspect ball valve for leaks.
Any fuel leak.
16
(DELETED)
17
During
Discharge Hose,
Inspect hose material and valved dry break
Any fuel leak.
2 in x 50 ft.
couplings for leaks.
18
During
Elbows
Inspect elbow body and non-valved
Any fuel leak.
couplings for leaks.
19
During
Tees
Inspect tee body and valved couplings for
Any fuel leak.
leaks.
20
During
Discharge Hose,
Inspect hose material, valved dry break
Any fuel leak.
3 in x 50 ft.
coupling and ball valve assembly for
leaks.
21
During
Grounding Rods
Check connection of grounding clamps.
Grounding clamp (s)
Clamps must be securely fastened.
disconnected.
Reconnect if required.
2-16 Change 4
|