4-6.
CAMLOCK
DISCONNECT ASSEMBLY REPLACEMENT
AND REPAIR. - continued
(2)
Check parts for excessive buildup of dirt and debris. Clean if needed.
Dry cleaning solvent used to clean parts is potentially
dangerous to personnel and
property.
Do not use near open flame or excessive heat. Use in well ventilated area.
NOTE
Prior to reassembly, clean all metal parts. They must be free from oil, grease and
corrosion resistant compounds on all interior and exterior surfaces.
(3) Wash all metal parts with dry cleaning solvent.
(4)
Dry thoroughly with clean, lint free cloth.
d.
Assembly
See figure 4-3.
NOTE
A light coat of petrolatum can be applied to all gaskets and preformed packings to
ease assembly.
(1)
Install strainer (12) and retaining ring (11).
(2) Slip a new preformed packing (10) into place on nozzle adapter (9) end.
(3) Slip housing (8) onto nozzle adapter (9) end and aline holes over ball race in nozzle adapter end.
NOTE
Retainer must be installed with bevel toward adapter flange.
(4) Slip retainer (6) onto housing (8).
(5)
Place sixteen balls (7) in holes using retainer (6) to help hold balls in place. Seat retainer into place over
balls.
(6) Secureretainer (6) with two screws (5).
(7) Secure screws (5) with twisted lock wire (4). Be sure that ends of lock wire are turned under and that no
sharp edges are exposed.
(8) Slip retaining ring (3) into groove nearest retainer (6) in housing (8).
(9) If old gasket (2) was damaged, replace with new gasket.
(10) Apply antisieze tape to camlock coupling (1) threads and install into housing (8).
e.
Installation
See figure 4-2.
Install new gasket (6), camlock disconnect assembly (5), six flat washers(4), screws (3), flat washers (2),
and new lock nuts (1).
4-6
|