TM 10-4930-246-13&P
Table 2-1.1 Operator PreventiveMaintenanceChecksandServicesfor D-1R Nozzle
Location
Item
Interval
Item to Check/Service
Procedure
Not Fully Mission Capable If:
No.
2 INLET
2 45 psi
ELBOW
\,,7ULATOR
4 HANDLE
3 GROUNDING
AND
BONDING CABLE
ASSEMBLY
4 HAND E
5
Before
Nozzle Body Assembly
Inspect connection end and verify
Index pins or collar lock pins
that index pins and collar lock pins missing, worn or damaged.
are intact, in place and not
excessively worn or damaged.
1@
Before
Verify that all three collar lock
Index pins are not extended to
pins are intact, undamaged and are
engage all three collar cutouts.
extended and em-,aLe all three
cutouts in the collar and physically
prevent collar rotation. If the
collar lock pins are not extended
and enga,,ed in all three cutouts in
the collar, the operator should
squeeze the lever and handle grip
together while observing the
connectin- end of the nozzle. This
should cause the collar lock pins to
spring Into the cutouts in the
collar.
Attempt to open the nozzle with
Nozzle opens.
the lever.
Change
1
2-12.1
|