TM 10-4930-240-13
Table 2-1. Operator Preventive Maintenance Checks and Services for Model AFARE100 - cont.
Location
Item
Interval
Procedure
Not Fully Mission
No.
Item to
Capable If:
Check/Service
34
During
500 Gallon
Perform "DURING" PMCS in accor-
Collapsible
dance with TM 10-110-203-12&P
Drums
35
During
Grounding Rods
Check connection of grounding
Grounding clamp (s)
clamps. Clamps must be securely
fastened.
disconnected.
36
During
Fire
Check for full charge. Inspect for
Fire extinguishers
Extinguishers
damage.
discharged or damaged.
37
After
OCR Nozzle and
Perform "AFTER" PMCS in accor-
Gravity Fill
dance with TM 10-4930-243-13&P
Adapter
38
After
Single Point
Perform "AFTER" PMCS in accor-
Refueling Nozzle
dance with TM 10-
4930-242-13&P
(D1)
39
After
Discharge Hoses
a. Inspect for cuts, tears and deep
Hose cut or torn
abrasions in hose material.
b. Inspect quick disconnect couplings
Gaskets damaged or
for damaged or missing gaskets.
missing.
c. Inspect for missing dust caps or
plugs.
d. Inspect for fuel leaks.
Any fuel leak
40
After
Wyes/Reducers
a. Inspect body for cracks and corro-
Body cracked
sion.
b. Inspect quick disconnect couplings
Gaskets damaged or
for damaged or missing gaskets.
missing.
c. Inspect for missing dust caps or
plugs.
d. Inspect for fuel leaks.
Any fuel leak.
41
After
Valve Sections
a. Inspect valve body for cracks
Valve body cracked.
b. Inspect for missing, loose or dam-
Handwheel missing.
aged handwheel.
c. Check operation of valve. Valve
Valve sticks or binds
should turn freely without sticking or
binding
2-31
|