TM10-4330-235-13&P
Table 3-1. Troubleshooting (Contd)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2.
Leaks at couplings.
Step 1. Check to see that cam handles are fully closed.
Drive cams home to secure coupling.
Step 2. Stop operation and check female couplings for gaskets.
Replace damaged or missing gaskets.
3.
Inadequate output.
Step 1. Check pump flow rate and performance.
Increase pump flow.
Step 2. Check for obstruction or kink in discharge line.
Remove obstruction or straighten line.
Step 3. Check differential pressure gage reading.
if indication is in red (above 35 psid) stop operation and notify unit maintenance.
Section Ill. Maintenance Procedures
3-2 GENERAL
Operator maintenance on the filter/separator consists of only the tasks and procedures stated in the operator
Preventive Maintenance Checks and Services (PMCS) chart. Refer to the operators PMCS chart and perform all
tasks outlined at the intervals specified.
3-2
|