Do not operate 350 GPM Pumping Assembly without grounding.
Do not operate equipment in enclosed area unless exhaust gases are
piped to outside and adequate ventilation is provided.
Avoid
inhalation of exhaust fumes.
Do not stand within 50 feet of operating equipment without
ear protection.
Failure to obey these warnings may result in hearing lose.
Do not operate starter motor for more than 10 seconds, damage to
starter can result.
Push in start switch (8) and oil pressure bypass switch (9) simultaneously.
After 10 seconds, release start switch.
(1) If engine does not start, release oil pressure bypass
minutes and repeat steps h and i.
If engine does not
repeated attempts, refer to operator troubleshooting.
(2) When engine starts, release start switch (8) .
switch, wait
s t a r t a f t er
two
The engine will shutdown when oil pressure bypass switch
is released if oil pressure is not 4 psi or above.
Release oil pressure bypass switch (9) when oil pressure is indicated on
gauge (10).
Allow engine to warm-up at idle RPM for two minutes.
Open suction valve (2) that is connected to suction line.
Observe the end of vent line (12) for liquid flowing from it.
Once liquid
begins to flow from line, close vent valve (1) .
Ensure discharge valve is open.
Pump can overheat if discharge
valve is closed for long periods of time.
A vapor-locked
condition may result.
If this occurs, shutdown engine and allow
pump to cool before filling housing with liquid.
Slowly open discharge valve (3) that is connected to discharge line.
place mode selector (6) to MANUAL position and rotate the manual speed
control (5) clockwise until gauge (11) indicates approximately 2400 RPM.