2-7. OPERATING PROCEDURES.
a.
Starting. Refer to Figure 2-8.
CAUTION
All doors and panels must be installed and turn-lock fastners locked. Failure to
observe this may result in damage to equipment.
NOTE
If panel lights are required, turn panel lights on.
(1) Connect battery (1) and push in circuit breakers (2).
(2) PRIMING SHUT OFF VALVE (3) turn handle to on.
(3) FUEL SELECTOR VALVE (4) turn handle to external.
(4) On 200/600 GPM fuel pump (5) loosen T-handle (6) and rotate handle (7) in open position (vertical position).
Tighten T-handle (6).
(5) Priming vent drain tank valve (8) set handle to close (vertical position).
(6) On the control panel (7) position PUMP CLUTCH switch (10) to disengaged.
(7) START switch (11) set to stop.
(8) Engine pump (12) and fuel heat switches (13) set to off.
(9) Pull MASTER switch (14) on.
(10)
If temperature is below 0°F (-32°C), set FUEL HEAT switch (13) to on and wait approximately 30
seconds. If below -20°F (-28°C), set FUEL HEAT switch (13) to on and wait approximately 1 minute and 30
seconds. After approximate time, turn fuel heat switch (13) to off.
(11) ENGINE PUMPS switch (12) set to on for fifteen seconds before starting engine.
WARNINGS
If emergency shutdown is required, push in MASTER switch to turn off the on
200/600 GPM Pump. Failure to observe this warning may result in serious
injury or death to personnel.
Ear protection is required when operating the 200/600 GPM Pump. Serious
hearing loss could occur if operated without ear protection.
2-41
|