2-5. Assembly and Preparation for Use (CONT).
WARNING
To prevent pumping assembly from rolling or sliding, securely chock both wheels or serious injury to
personnel could result.
(8)
Place chocks (6) under wheels (7).
WARNING
Pumping assembly Model 13229E8400 (97403), must be grounded prior to operation when fuel is pumped
or spark could ignite fuel causing possible injury to personnel.
(9)
Remove a ground rod (8) from frame assembly, except Model 13229E8401 (97403), and drive into ground
approximately four feet. Remove grounding cable (9) from tool box and clamp one end to the rod and the other
to the frame grounding lug (10).
(10)
Ensure the two fuel selector valves (11) are positioned correctly. Valve handles must have pointer in the "FUEL
TANK" position when fuel is supplied from the pump tank.
(11)
Perform preventive maintenance checks and services (Table 2-1).
2-10
|