2-6.
FINAL SITE PREPARATION.
CAUTION
Electrical equipment used within 50 feet (15.24 meters) of the tank should be approved
for use in Class 1, Group D, Division 1, hazardous locations as defined by the National
Electrical Code.
a.
Clear the site area within 100 feet (30.48 meters) of the tank of all dry grass, brush, and weeds. Remove all
spark-producing equipment or devices from the cleared area. Post signs stating "FLAMMABLE LIQUID - NO
SMOKING OR OPEN FLAME WITHIN 100 FEET OF TANK".
b.
Have fire extinguishing equipment on hand. Equipment should include a quick-smothering type of
extinguishing agent, such as carbon dioxide or dry chemical, or a permanent type of extinguishing agent, such as
foam. Locate equipment approximately 50 feet (15.24 meters) from tank.
c.
Secure area by fencing or other means to prevent access by unauthorized personnel.
d.
Post signs indicating where to seek help in case of emergency.
2-14
|