TM5-4930-235-13&P
Table 2-1. Operator/Crew Preventive Maintenance Checks and Service
NOTE: Within designed interval, these checks are to be performed in the sequential order listed.
B-Before
D-During
A-After
W-Weekly
M-Monthly
Item
Interval
Item to be
Procedures
For Readiness Reporting,
No.
B
D
A
W
M
Inspected
Check For and Have
Repaired or Adjusted
Equipment is Not
Ready/Available if:
1
Nozzle
Assembly
Check for damaged body,
signs of leaks or cracks.
(Vacuum break valve
moves.)
Outward signs of damage
or leakage.
2
Outlet Cap
Check for signs of cracks,
loose or frayed cable.
3
Ground Clip
Assembly
Check for loose or frayed
cable. Check for damage to
clip or cable eye. Check
screw for tightness.
Outward signs of damage
or screw loose.
4
Coupling
(Cam-lock)
Check for signs of cracks,
loose or frayed cable.
Check to ensure coupling
gasket is in place.
Outward signs of damage.
5
Coupling Assy
(Unisex)
(Model 125-
0505)
Check for signs of leakage,
and loose, frayed or broken
cables. Check to ensure
coupling gasket is in place.
Outward signs of leakage
and damage.
6
Ground Plug
Assembly
Check for loose or frayed
cable. Check for damage to
plug or cable eye.
Outward signs of damage.
7
Strainer
Check for damaged and/or
dirty screen.
Section III. OPERATION UNDER USUAL CONDITIONS
2-4. Connection of Nozzle. (Cam-Lock). (See Figure 2-2.)
a.
Pull cam arms (1) away from coupling half (2) and remove dust plug (3).
b.
Slide end of fuel hose (4) into end of coupling half (2).
c.
Push cam arms (1) against coupling half (2).
Change 1
2-3
|