Table 5-1. Troubleshooting (Cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
10. LEAKAGE FROM OUTLET END WHILE DISCONNECTED FROM RECEPTACLE.
Step 1. Look inside outlet end. See if leakage is coming from around outside of safety sleeve.
NOTE
This procedure can only be done during CCR Nozzle Sub-Assembly maintenance (See paragraph 5-6).
Remove plunger and safety sleeve. Inspect position of seal (facing the correct direction). If not, remove and
install seal in correct position. If seal is cut or torn, replace it. Install safety sleeve and plunger.
Step 2. Look inside outlet end. See if leakage is coming from around plunger.
NOTE
This procedure can only be done during CCR Nozzle Sub-Assembly maintenance (See paragraph 5-6).
Remove plunger and safety sleeve. Inspect parts for wear, cracks, or distortion. Replace any damaged parts.
Assemble nozzle.
11. NO ELECTRICAL CONTINUITY BETWEEN GROUND CLIP/GROUND PLUG AND NOZZLE.
Inspect ground cables, cap screw, and inlet coupling for dirt or corrosion.
Remove cap screw, ground cables, and inlet coupling. Remove any dirt or corrosion from ground cables,
screw, threads of inlet coupling, and body. Assemble parts and test for continuity. Replace any damaged
components.
12. PULLBACK SLEEVE DOES NOT ACTIVATE OR LOCK ON TO RECEPTACLE.
Disassemble nozzle and inspect parts.
NOTE
This procedure can only be done during CCR Nozzle Sub-Assembly maintenance (See paragraph 5-6).
Check for cracks, distortion, out of round condition, or improper assembly of parts. Replace all damaged
parts and assemble in the proper order.
5-4
|