Table 2-2
SIX (6) INCH HOSELINE LENGTHS IN FEET, DIESEL (D-2) VERSUS RATE OF FLOW
Required Pressure, psig
Flow
Rate, Gpm
25
50
75
100
125
150
200
15,500
--
--
--
--
--
300
7,500
15,000
--
--
--
--
400
4,500
9,000
13,500
--
--
--
500
3,000
6,000
9,000
12,000
--
--
600
2,200
4,400
6,600
8,800
11,000
--
700
1,600
3,200
4,800
6,400
8,000
9,600
800
1,300
2,600
3,900
5,200
6,500
7,800
900
1,000
2,000
3,000
4,000
5,000
6,000
1000
800
1,600
2,400
3,200
4,000
4,800
Table 2-3
SIX (6) INCH HOSELINE LENGTHS IN FEET, JET FUEL (JP-4) VERSUS RATE OF FLOW
Required Pressure, psig
Flow
Rate, Gpm
25
50
75
100
125
150
200
17,300
--
--
--
--
--
300
8,400
16,800
--
--
--
--
400
5,000
10,000
15,500
--
--
--
500
3,400
6,800
10,200
13,600
--
--
600
2,400
4,800
7,200
9,600
12,000
--
700
1,800
3,600
5,400
7,200
9,000
10,800
800
1,400
2,800
4,200
5,600
7,500
8,400
900
1,100
2,200
3,300
4,400
5,500
6,600
1000
900
1,800
2,700
3,600
4,500
5,400
2-53
|