| |
APPENDIX A
Meter
Installation/Operation
June 1985
Bulletin 1.2.11
Caution
Read Instructions carefully before attempting
to operate. Each meter Is thoroughly tested
before leaving the factory. Smith Meter Inc.
cannot accept claims for damage occurring
during the fire 24 hours of operation.
Installation Instructions
1.
The meter and its accessories are precision instruments and
should be treated accordingly. Prior to installation the equipment
should be protected from adverse weather conditions and
accidental abuse.
2.
The installation should provide protection from sand, dust, rain,
sleet, etc., where extreme adverse weather conditions are
encountered.
3.
Except for vertical meter installations the meter should be
mounted on a suitable base or platform so it will not be supported
by the piping.
a.
Dimensional outline drawings showing size and location
of anchor holes are available for all meters.
4.
Install the meter so that it cannot be accidentally drained of
product; however, it is advisable to drain the meter of water and
sediment periodically.
a.
When installing a meter, be sure drain plug is accessible.
5.
Piping should not produce an undue strain on the meter.
6.
Protect the meter and system against the effects of thermal
expansion with a relief valve.
7.
Where necessary, a deaerator or air eliminator should be installed
to keep air and vapor out of the meter.
8.
All piping should be internally cleaned before the meter is put into
operation.
a.
Rust, dirt, welding shot, and other foreign material should
be removed completely.
b.
Remove the inner mechanism and flush the lines to
prevent damage to the metering element.
c.
The meter should be protected by a strainer.
9.
Where necessary, a flow limiting valve should be installed
downstream of the meter to protect it from excessive flow rates.
10.
Remove the inner mechanism if the system is to be pressure
tested with water or if debris is to be flushed from system.
11.
Do not calibrate with water or allow water to stand in the meter.
a.
Flush meter with a light lubricating oil if it is left idle or
stored.
12.
Unless otherwise specified, meters normally flow from left to right
when viewed from the flanged side of the housing.
a.
Most meters can be changed to flow from right to left.
See the appropriate manual.
13.
A counter may be located in any one of four 90° positions. Large
numeral counters may be located in any of eight 45° positions.
Operation Instructions
Start-Up
It is best to fill the meter by gravity. However, where hydraulic conditions
require that the pump(s) be operated, extreme care should be used in
opening the valves at the meter.
In all instances, the air should be evacuated slowly from the meter and
system.
1.
Establish product flow through meter.
a.
With outlet valve closed, slowly open inlet valve.
b.
Slowly open outlet valve until counter begins to turn.
Leave outlet valve in throttled position until air is
evacuated from meter.
This is necessary to protect the meter from excessive
speed due to air in the lines of system.
2.
Loosen vent plug of double case meters (except for vertical
meters) when meter is filled with liquid.
a.
Permit the air trapped in the meter cover to escape
through the threads. Close plug when product begins to
seep through threads.
3.
Fully open inlet and outlet valves.
a.
Open valves slowly, pausing if register operation is rough.
Continue opening when operation becomes smooth.
4.
Inlet and outlet valves should be operated slowly to avoid line
shock. Abrupt closure can create forces in excess of normal line
pressure. This could result in damage to the meter and other
equipment.
5.
Do not set a reset type counter when the meter is operating.
6.
The ticket securing pin in a printer head must be in the down or
locked position when the meter is operating.
7
Meters equipped with G, ATG, AMR, or Dummy calibrators can
be operated in either direction.
8.
Calibration adjustment has been made at the factory for zero error
at maximum nameplate capacity on 33 SSU solvent. Due to
variations in operating conditions it is recommended that the
meter be calibrated and adjusted after installation.
9.
Meter calibration is accomplished by adjusting the calibrator dial
or knobs. Calibration may be changed in increments of 1/20 of
1%. The adjustment is concealed under a cover on the calibrator
adapter.
10.
To obtain maximum service from Smith meters, it is suggested
that detailed records be maintained. Data such as model, serial
number, operating rate, type of product, meter clearances,
totalizer readings and other pertinent information should be
recorded. Such information is an excellent guide in scheduling a
preventive maintenance program. Refer to manuals for meter
maintenance.
Note
For further information on meter installation,
meter proving, and operation the following
publication is recommended: API Standard
1101, Measurement of Petroleum Liquid Hydro-
carbons by Positive Displacement Meter.
1602 Wagner Avenue, P.O. Box 10428, Erie, PA 16514, Telephone: 814/899-0661, Telex: 19-9902
A9-15/(A9-16 Blank)
|