TM 07661B-14/1
APPENDIX A
Table A 1-1. Reference Data Model 450 PKP/ 100 AFFF 0363MC
Fire Extinguisher
Manufacturer...............................................................................................................................Fire Combat, Inc.
Model......................................................................................................................... 450PKP/100AFFF03638MC
Type..................................................................................................................................................... Twin Agent
Dimensions (Base Unit).............. 95 in. long, 48 in. wide, 51 in. high
(Remote Hose Cart) 48 in. long, 45 in. wide, 59 in. high
Weight (Basic Unit)
Without chemical agents (Full N2 Cylinders) ................................................................................1970 lbs.
Fully serviced ..............................................................................................................................3260 lbs.
Weight (Remote Hose Cart) .......................................................................................................................455 lbs.
Twinned Hose Length:
Basic Unit ........................................................................................................................................ 150 ft.
Remote Hose Cart ........................................................................................................................... 150 ft.
Operating Pressure (Tanks and Hoses) ................................................................................................220-240 psi
Capacities:
Dry Chemical (Potassium Bicarbonate)..........................................................................................450 lbs.
6% AFFF Solution ................................................................................................................... 100 gallons
Nitrogen (N2).......................................................................................................2 ea. 300 cu. ft. cylinders
Nitrogen (N2) Specifications ............................................................................................ Type 1, class 1, grade B,
of BB-N-411
Heater Power Requirements ......................................................................................... 120/240 volts, 1 phase, 60
hertz, 1300 watts
Flow Rates:
AFFF (150 ft. hose) .................................................................................................... 51 gals. per minute
(300 ft. hose) .................................................................................................... 40 gals. per minute
Dry Chemical (150 ft. hose) ........................................................................................ 5.7 lbs. per second
(300 ft. hose)........................................................................................ 4.4 lbs. par second
Continuous Flow Time:
150 ft. hose:
AFF Minute, ................................................................................................ 1 Minute, 58 Seconds
Dry Chemical .............................................................................................. 1 Minute, 19 Seconds
300 ft. hose:
AFFF ........................................................................................................ 2 Minutes, 30 Seconds
Dry Chemical .............................................................................................. 1 Minute, 42 Seconds
A 1-4
|