2-1.4 General Design Conditions Summary - Cont'd.
Optional Configuration
Six (6) 50,000 Gal.
7,143
300,000
Sub-Total
97,143
4,080,000
Contaminated Fuel Storage
Two (2) 50,000 Gal.
2,.381
100,000
Total Available Storage
99,524
4,180,000
b. Design Flow Rates
One TPT
Fuel receiving rate (typical TPT, to single fuel unit)
800 gpm
Internal transfer rate
600 gpm
Discharge to pipeline system (ea. fuel unit w/l1 pump)
600 gpm (1)
Discharge to pipeline system (ea. fuel unit, from 2
tank modules, 2 parallel pumps)
800 gpm (1)
Fuel dispensing rate (ea. fuel unit)
600 gpm (2)
NOTES
(1)
Nominal dependent on associated pipeline system pressure requirements may require installation of
booster pump (spare 600 gpm hoseline pump). Site and pipeline system governs.
(2)
Nominal based on pump capacity flow and pressure to be regulated at pump to maintain safe but adequate
rates at dispensing nozzles for particular installation and loading circumstance. Rate with one filter
separator in service is restricted to 350 gpm.
c. Design Operating Pressure
Discharge and transfer hose
150 psig max.
Suction hose (normally utilized
in pump suction service only
at pressures at or below static
liquid head)
100 psig max.
Valves and fittings (except
dispensing set
150 psig max.
Fuel dispensing set)
75 psig (1)
Equipment incl. 600 gpm hoseline
pumps, filter separators, and
meter strainer assemblies
150 psig max.
Fabric collapsible tanks
Static liquid
head plus
0.10 psig
2-10
|