TM 10-6630-240-12&P
TM 01461B-12&P/1
k.
Disconnect the bypass hose (1) from the side of the sampler base (2) and unscrew the sampler base from the
sampler cover (3). Hold the sampler in an upright position and remove the stainless steel monitor (4). (figure 2- 31)
Figure 2-31
NOTE
To maximize the accuracy of the reading, the free water test pad should be read within 3
minutes of initiating the sampling.
1.
Disassemble the stainless steel monitor and gently remove the free water pad. Place the pad between two dry
clean paper towels and blot out excess fluids.
NOTE
A pad not properly blotted will result in a low reading because the excess fuel will absorb part
of the ultraviolet light and decrease fluorescence.